Gas burner won't light: what to check, in the order the burner starts

An industrial gas burner starts in a fixed sequence: air proving, pre-purge, spark, gas valves open, flame proven. When it fails to light, the quickest way to find the fault is to watch where in that sequence it stops, then check only what belongs to that step.

Safety first. Gas burner work belongs to a qualified burner technician. Never bypass a pressure switch, flame signal or valve-proving step to get a burner running, and never repeat resets over and over: each failed start can leave unburnt gas in the chamber. Close the manual gas valve before opening up the gas train.

1. Find where the sequence stops

Most burner controls show the step and the fault: a code on the display, a blink code, or lamps on the front. Write it down before resetting. Our pages on Honeywell 7800 fault codes and Siemens LME blink codes list the common ones.

Where it stopsLook at first
Fan runs, no purge timer startsAir pressure switch, blocked air inlet or filter, fan belt or rotation
Purge completes, no sparkIgnition transformer, HT lead, electrode gap and insulator
Spark, but no flameGas not reaching the burner: manual valve, low gas pressure switch, solenoid valves, regulator, air in the line
Flame lights, then locks out after a few secondsFlame signal: flame rod or UV scanner, earth, air/gas ratio at ignition

2. No air proving

3. No spark

4. Spark but no flame

5. Flame lights, then goes out

Parts that often turn up in these faults

Still stuck? Send the burner nameplate, the control model, the fault code and a short video of the start-up on WhatsApp. We tell you the likely cause and the part, original or compatible, before you order.

Honeywell, Siemens, Dungs, Kromschröder and COFI are trademarks of their owners. SENNISI is an independent company and is not affiliated with these manufacturers.

Frequently asked questions

What should I check first when a gas burner won't light?

Go in start-up order: power and safety interlocks, air proving, purge, ignition spark, gas pressure at the valve inlet, valve opening and flame detection.

Why does the burner light and then go out after a few seconds?

Usually the flame is not detected: check the flame scanner or flame rod signal, grounding and the air-gas ratio at low fire.