The 7800 SERIES relay modules (RM7800, RM7840, RM7890, RM7895, RM7838, EC7850 and others) stop the burner and show a numbered fault on the S7800A keyboard display. Most lockouts are caused by something around the control, not by the control itself.
Safety first. A lockout is the burner control doing its job. Never bridge an interlock, a pressure switch or the flame signal to keep a burner running. Diagnosis and repair of flame safeguards belong to a qualified burner technician.
| Fault | Display text | What it means | Check first |
|---|---|---|---|
| 15 | Flame Detected | A flame signal was seen when no flame should be there. | Detector sighting hot refractory, a leaking fuel valve, a faulty UV tube or wiring picking up noise. |
| 16 | Flame-Out Timer | No flame was proven during the pilot flame establishing period. | Pilot gas pressure, ignition spark, detector sighting. |
| 17 | Main Flame Fail | Flame was lost while the burner was running. | Gas pressure dropping at high fire, air/gas ratio, a dirty or failing flame detector. |
| 18 | Flame Detected | Flame sensed during pre-purge when none was expected. | As for Fault 15; on a self-checking detector, the shutter. |
| 19 | Main Flame Ign. | Flame was lost while the main flame was being established, or in the first seconds of running. | Main gas pressure and valve opening, air/gas setting at light-off, detector signal strength. |
| 20 | Low Fire Sw. Off | The low-fire interlock switch did not close during pre-purge. | Actuator (for example a Modutrol motor) returning to low fire, the switch and its linkage. |
| 21 / 22 | Running ILK / Lockout ILK | An interlock opened during pre-purge. | Air pressure switch, gas pressure switches, limit switches wired into that interlock string. |
| 28 | Pilot Flame Fail | The pilot did not light or was not proven. | Pilot gas pressure, ignition transformer and electrode, flame detector and its sighting, flame amplifier. |
| 29 | Lockout ILK | The lockout interlock string opened. | Combustion air flow and air pressure switch, fan inlet blocked, high/low gas pressure switches, loose or broken wiring. |
| 41 / 42 / 43 | Main Valve On / Pilot Valve On / Ignition On | An output terminal was powered when it should not be. | External wiring feeding back into the terminal. If wiring is right, the relay module. |
| 47 | Jumpers Changed | Configuration jumpers on the module were changed after setup. | Whether someone has cut a jumper; the module may need replacing. |
| 51 | Flame Too Strong | Flame signal too high to be valid. | Flame amplifier and detector type match, detector or amplifier fault. |
Wording and numbering can differ slightly between models and firmware. The Honeywell troubleshooting table for your exact relay module is the reference: the 7800 SERIES manuals are linked from our 7800 SERIES page.
If the display stays in STANDBY and never starts pre-purge, the module is usually still waiting for its start conditions: the operating control or limit circuit calling for heat, and the interlocks it checks before purge. Work through those inputs with a meter before suspecting the module.
After the wiring, pressures, detector and amplifier check out, and the same fault comes back after reset, the relay module itself may have failed. Older RM7840L1018, RM7840L1075, RM7890A1015, RM7895A1014 and EC7850A units are common on furnaces and ovens installed fifteen or twenty years ago.