Siemens LME blink codes: what the red lamp is telling you

LME burner controls stop the burner and turn the signal lamp red when something in the start-up sequence goes wrong. The number of red flashes tells you which part of the sequence failed. In most cases the cause is around the control, not the control itself.

Safety first. A lockout is the control doing its job. Never bridge an air pressure switch, a gas pressure switch or the flame signal to keep a burner running. Diagnosis of flame safeguards belongs to a qualified burner technician.

How to read the code

When an LME11, LME21 or LME22 locks out, the red lamp in the reset button stays on. On these units, holding the reset button for more than about three seconds switches the lamp to diagnostic mode: it then flashes red a number of times, pauses, and repeats. Count the flashes between pauses. A short press resets the lockout.

Red flashesWhat it meansCheck first
2No flame established at the end of the safety time.Gas reaching the burner (pressure, manual valve open, solenoid valves opening), ignition spark, ionization electrode or detector position and wiring, air-gas setting at light-off.
3Air pressure switch fault: the air signal was lost, or the switch did not start in the right position.Fan running and turning the right way, air inlet or flue blocked, air pressure switch setting, hose and switch contacts.
4Extraneous light at start-up: a flame signal was seen when there should be none.Gas valve leaking and keeping a flame alive, detector seeing hot refractory or daylight, a faulty detector.
5Air pressure switch time-out: the switch stayed in its working position.Air pressure switch contacts welded or stuck, wrong wiring of the switch.
7Too many flame losses during operation.Gas pressure dropping at high fire, air-gas ratio, a dirty or ageing ionization electrode or detector, poor earth on the burner.
10Wiring error or internal fault.Mains phase and neutral swapped, external voltage fed back onto an output terminal. If the wiring is right, the control itself.
14Valve closure contact (POC) not closed, on versions that check it.Proof-of-closure switch on the gas valve and its wiring.

Codes and functions vary between LME types and generations (LME4 and the programmable LME7 have their own diagnostics on a display). The Siemens data sheet for your exact type is the reference.

Ionization: the cause we find most often

On gas burners with an ionization electrode, many code 2 and code 7 lockouts come from a weak flame current: an electrode bent out of the flame, a cracked ceramic, a corroded connector, or a burner body with poor earth. The flame current must be several microamps above the control's minimum. Measuring it with a microammeter in series with the electrode lead is the quickest way to tell a burner problem from a control problem.

When the LME itself is the problem

If the gas supply, air pressure switch, ignition and flame signal all check out and the same code comes back, the control may have failed. Replacements must have the same type code, because the digits after the point set the pre-purge and safety times. An LGB or LMG being replaced by an LME should be matched to the burner, not just to the base.

Parts that often go with these faults

Running a Honeywell control instead? See Honeywell 7800 fault codes.

Need the control or a part quickly? Send a photo of the label on WhatsApp. We supply the original part where it is available, or a compatible replacement, and say which before you order.

Siemens is a trademark of Siemens AG; Dungs and MultiBloc are trademarks of Karl Dungs GmbH & Co. KG. SENNISI is an independent company and is not affiliated with these manufacturers.

Send us your nameplate.

A nameplate photo, or your heat load, fuel and gas pressure. The reply comes from an engineer.

WhatsApp an engineer →   [email protected]