Burner controls

Siemens LAL / LFL burner controls (LAL1.25 / LAL2.25 / LAL2.65 / LFL1.333 / LFL1.335 / LFL1.635)

Electromechanical (cam-timer) burner controls: LAL for oil burners, LFL for gas, oil and dual-fuel forced-draught burners; plug-in base, ionization, QRA UV or QRB photocell detection.

WhatsApp an engineer Replacement quote

How we help

For a burner control or relay module, send the full part number from the label (for example RM7840L1018), the supply voltage and the flame detector used. Controls must match the original sequence and safety timings, so we always check these before quoting.

Where it is used

LAL and LFL are the classic electromechanical sequence controls with a motor-driven cam timer. LAL is used on oil burners, LFL on gas, oil and dual-fuel forced-draught burners. Thousands are still running on steam boilers, thermal-oil heaters, asphalt dryers and process furnaces in Southeast Asia and the Middle East.

Why it gets replaced

After many years the synchronous motor, cam contacts or relays wear out. Typical symptoms: the programme stops part-way, the burner locks out with no clear cause, or the lockout indicator does not reset. A replacement must have the same timings, otherwise the purge and safety times of the burner change.

Send us before we quote

  • Exact type, for example LFL1.333 or LFL1.635 (the timings differ between types)
  • Supply voltage: 110 V or 230 V
  • Flame detector used: ionization, QRA2 / QRA10 UV or QRB photocell
  • Photo of the plug-in base and wiring
  • Burner make, model and fuel

Often replaced together with

  • QRA UV detector or QRB photocell
  • Plug-in base
  • Air pressure switch
  • Ignition transformer

If the original is still made, we get it for you. If it is not, we offer a part that fits the same mounting and wiring, and tell you what is different before you order.

Model numbers we are often asked about

LAL1.25, LAL2.25, LAL2.65, LFL1.122, LFL1.322, LFL1.333, LFL1.335, LFL1.635. Not on the list? Send the full model string from the nameplate.

Brand and model names are used only to identify the equipment. They are trademarks of their respective owners; SENNISI is an independent company and is not affiliated with these manufacturers.

Related models

Send us your nameplate.

A nameplate photo, or your heat load, fuel and gas pressure. The reply comes from an engineer.

WhatsApp an engineer →   [email protected]