Most burner stoppages come from a handful of causes: dirty filters, drifting gas pressure, a worn electrode or flame detector, or an interlock that has been set wrong. A short routine catches them before they stop production.
Safety first. Work on gas trains and flame safeguards belongs to a trained burner technician. Never bridge an interlock, pressure switch or flame signal to keep a burner running. Isolate gas and power before opening the burner.
| When | Check |
|---|---|
| Daily / each shift | Clean area around the burner; gas and air pressures on the gauges; flame looks normal through the sight glass; no unusual noise; note readings in the shift log |
| Monthly | Clean the combustion air filter and blower inlet; check wiring and fastenings for looseness; check gas pipework for leaks with leak-detection spray |
| Every 3–6 months | Clean the gas filter; clean dust from the fan impeller; inspect electrode, flame rod or UV scanner and the mixing head; check the combustion chamber and flue for soot or blockage |
| Yearly | Test every safety interlock (low and high gas pressure, air pressure, high temperature) and record the results; leak-test the safety shut-off valves for tightness; check flame failure response by shutting off the gas and confirming lockout; combustion analysis and air/fuel ratio check |
In the US, NFPA 86 sets annual testing of furnace safety devices as a minimum, and the testing must be documented; seat-leakage testing of safety shut-off valves is a separate annual requirement. A manufacturer's schedule can call for shorter intervals, and the stricter one applies. Other countries have their own rules (EN 746-2 in Europe); follow the one that applies at your site.
Confirm that the burner is being operated correctly, power is normal, gas flow and pressure are normal, the external control wiring is intact, the combustion chamber and flue are clear, and the burner is the right size for the equipment.
| Symptom | Likely cause | What to do |
|---|---|---|
| Switch on, blower motor does not run | No power | Check the main switch and fuses |
| Motor overload relay tripped | Check the setting; if correct, reset | |
| Temperature or pressure controller faulty or mis-set | Readjust or replace | |
| Low gas pressure switch open | Check the gas supply valve is open and the filter is not blocked | |
| Control in lockout (alarm on, red lamp lit) | Find the cause of the last flame failure, then reset | |
| Air damper does not move to high fire (modulating) | High-fire limit switch mis-set | Adjust so the switch closes when the damper reaches high fire |
| No ignition spark (alarm) | Air pressure switch not made | Check its operation; replace if faulty |
| Electrode touching metal, or cracked | Reset the gap; replace a cracked electrode | |
| Ignition cable damaged | Replace | |
| Flame safeguard relay faulty | Replace | |
| Spark present, pilot does not light | Pilot test cock closed | Open it |
| Air in the gas line | Purge the line safely | |
| Pilot lights, then goes out before main flame | Pilot gas pressure too high or too low | Adjust the pilot regulator |
| Poor pilot flame | Adjust pilot air | |
| Weak flame signal (flame rod below about 3 µA) | Adjust air; check the flame rod position | |
| UV scanner or flame rod faulty | Replace | |
| Flame safeguard relay faulty | Replace | |
| Pilot on, main burner does not light (alarm) | Main gas test cock closed | Open it |
| Main safety valve not opening although energised | Replace the valve | |
| Main flame lights, then goes out | Low gas pressure switch trips | Check supply pressure and the switch setting |
| Air pressure switch trips | Check the switch; clean a blocked air inlet or filter | |
| Linkage slipped | Re-set the linkage | |
| Temperature controller hunting, safety valve faulty | Replace the faulty part | |
| Sometimes will not restart (no alarm) | Gas pressure fluctuating and tripping the pressure switch | Log gas pressure over 24 hours |
| Voltage dips or short power cuts | Below about 85% voltage, motors and relays drop out; check the supply | |
| Random flame failures (alarm) | Pilot badly set, weak air switch, worn flame detector, cracked electrode insulator, faulty valve or regulator, ignition cable, linkage out of position | Check the flame current first, then work through the list |
| Gas smell before start | Leak at the safety valves or pipework up to the first valve | Find it with leak-detection spray and repair before firing |
| Gas smell after shutdown | Safety valve seat leaking | Leak-test the valves; replace and clean |
Ignition electrode and cable, flame rod or UV scanner, gas filter element, air filter, one solenoid valve coil and a spare flame safeguard relay. These cover most stoppages. We stock them for SENNISI burners and supply originals or equivalents for Maxon, Eclipse, Honeywell and Kromschröder systems: burner spare parts.
Check gauges and the flame every shift, clean filters monthly to quarterly, and test all safety interlocks and safety shut-off valve tightness at least once a year, with the results recorded.
The most common causes are a weak flame signal (dirty or badly placed flame rod, worn UV scanner), low gas pressure tripping the pressure switch, or an air pressure switch tripping because the air inlet or filter is blocked.
For many flame rod systems a steady signal of about 3 microamps or more is needed; check the value specified for your flame safeguard.
No. Interlocks exist to prevent explosions. Find and fix the cause, or call a burner technician.
A nameplate photo, or your heat load, fuel and gas pressure. The reply comes from an engineer.