Burner control cabinet and gas train during a maintenance check
Guides

Gas burner maintenance checklist and troubleshooting table

Most burner stoppages come from a handful of causes: dirty filters, drifting gas pressure, a worn electrode or flame detector, or an interlock that has been set wrong. A short routine catches them before they stop production.

Safety first. Work on gas trains and flame safeguards belongs to a trained burner technician. Never bridge an interlock, pressure switch or flame signal to keep a burner running. Isolate gas and power before opening the burner.

Before each start

Routine checks

WhenCheck
Daily / each shiftClean area around the burner; gas and air pressures on the gauges; flame looks normal through the sight glass; no unusual noise; note readings in the shift log
MonthlyClean the combustion air filter and blower inlet; check wiring and fastenings for looseness; check gas pipework for leaks with leak-detection spray
Every 3–6 monthsClean the gas filter; clean dust from the fan impeller; inspect electrode, flame rod or UV scanner and the mixing head; check the combustion chamber and flue for soot or blockage
YearlyTest every safety interlock (low and high gas pressure, air pressure, high temperature) and record the results; leak-test the safety shut-off valves for tightness; check flame failure response by shutting off the gas and confirming lockout; combustion analysis and air/fuel ratio check

In the US, NFPA 86 sets annual testing of furnace safety devices as a minimum, and the testing must be documented; seat-leakage testing of safety shut-off valves is a separate annual requirement. A manufacturer's schedule can call for shorter intervals, and the stricter one applies. Other countries have their own rules (EN 746-2 in Europe); follow the one that applies at your site.

Before you start fault-finding

Confirm that the burner is being operated correctly, power is normal, gas flow and pressure are normal, the external control wiring is intact, the combustion chamber and flue are clear, and the burner is the right size for the equipment.

Troubleshooting table

SymptomLikely causeWhat to do
Switch on, blower motor does not runNo powerCheck the main switch and fuses
Motor overload relay trippedCheck the setting; if correct, reset
Temperature or pressure controller faulty or mis-setReadjust or replace
Low gas pressure switch openCheck the gas supply valve is open and the filter is not blocked
Control in lockout (alarm on, red lamp lit)Find the cause of the last flame failure, then reset
Air damper does not move to high fire (modulating)High-fire limit switch mis-setAdjust so the switch closes when the damper reaches high fire
No ignition spark (alarm)Air pressure switch not madeCheck its operation; replace if faulty
Electrode touching metal, or crackedReset the gap; replace a cracked electrode
Ignition cable damagedReplace
Flame safeguard relay faultyReplace
Spark present, pilot does not lightPilot test cock closedOpen it
Air in the gas linePurge the line safely
Pilot lights, then goes out before main flamePilot gas pressure too high or too lowAdjust the pilot regulator
Poor pilot flameAdjust pilot air
Weak flame signal (flame rod below about 3 µA)Adjust air; check the flame rod position
UV scanner or flame rod faultyReplace
Flame safeguard relay faultyReplace
Pilot on, main burner does not light (alarm)Main gas test cock closedOpen it
Main safety valve not opening although energisedReplace the valve
Main flame lights, then goes outLow gas pressure switch tripsCheck supply pressure and the switch setting
Air pressure switch tripsCheck the switch; clean a blocked air inlet or filter
Linkage slippedRe-set the linkage
Temperature controller hunting, safety valve faultyReplace the faulty part
Sometimes will not restart (no alarm)Gas pressure fluctuating and tripping the pressure switchLog gas pressure over 24 hours
Voltage dips or short power cutsBelow about 85% voltage, motors and relays drop out; check the supply
Random flame failures (alarm)Pilot badly set, weak air switch, worn flame detector, cracked electrode insulator, faulty valve or regulator, ignition cable, linkage out of positionCheck the flame current first, then work through the list
Gas smell before startLeak at the safety valves or pipework up to the first valveFind it with leak-detection spray and repair before firing
Gas smell after shutdownSafety valve seat leakingLeak-test the valves; replace and clean

Spare parts worth keeping

Ignition electrode and cable, flame rod or UV scanner, gas filter element, air filter, one solenoid valve coil and a spare flame safeguard relay. These cover most stoppages. We stock them for SENNISI burners and supply originals or equivalents for Maxon, Eclipse, Honeywell and Kromschröder systems: burner spare parts.

Frequently asked questions

How often should an industrial gas burner be serviced?

Check gauges and the flame every shift, clean filters monthly to quarterly, and test all safety interlocks and safety shut-off valve tightness at least once a year, with the results recorded.

Why does my burner light and then go out?

The most common causes are a weak flame signal (dirty or badly placed flame rod, worn UV scanner), low gas pressure tripping the pressure switch, or an air pressure switch tripping because the air inlet or filter is blocked.

What flame current should a flame rod give?

For many flame rod systems a steady signal of about 3 microamps or more is needed; check the value specified for your flame safeguard.

Can I keep running by bridging a pressure switch?

No. Interlocks exist to prevent explosions. Find and fix the cause, or call a burner technician.