Iron-core ignition transformers for gas burners and gas-ignited oil burners, 5 / 7 / 7.5 kV, 115 V (R) or 230 V (W), 20 %, 33 % or 100 % duty; TZI for cabinet mounting, TGI enclosed for mounting beside the burner; often paired with IFD 258 or BCU.
For an ignition transformer, send the model from the label, the supply voltage, single or double output, and the kV and mA printed on it. Electronic transformers are often a direct swap for older iron-core types, but the cable connection and mounting must match.
TZI and TGI transformers make the ignition spark on industrial gas burners in furnaces, kilns and dryers, usually switched by a Kromschröder IFD 258 or BCU burner control.
Windings burn out when the duty cycle is exceeded (a /20 unit sparking continuously) or after heat and moisture near the burner; older TZI / TGI types are being replaced by the TZI ..QZ / WZ versions.
If the original is still made, we get it for you. If it is not, we offer a part that fits the same mounting and wiring, and tell you what is different before you order.
TZI 5-15/20W, TZI 5-15/100W, TZI 7-25/20W, TZI 7,5-12/100W, TZI 7,5-20/33W, TZI 5-15/100R, TZI 7-25/20R, TZI 7,5-20/33R (84391141), TGI 5-15/100, TGI 7-25/20, TGI 7,5-12/100, TGI 7,5-20/33; current versions TZI 5-15/100QZ, TZI 8-20/19QZ, TZI 8-20/33QZ, TZI 8-12/100WZ. Not on the list? Send the full model string from the nameplate.
Original documentation (Technical information): manufacturer's product page ↗
Brand and model names are used only to identify the equipment. They are trademarks of their respective owners; SENNISI is an independent company and is not affiliated with these manufacturers.
A nameplate photo, or your heat load, fuel and gas pressure. The reply comes from an engineer.
WhatsApp an engineer → [email protected]