For a direct-fired dryer exhausting air to atmosphere, the burner heats the fresh air drawn in:
Qair (kW) = air mass flow (kg/s) × 1.005 kJ/kg·K × temperature rise (K)
Air at 20 °C has a density of about 1.2 kg/m³, so 10,000 m³/h of fresh air is about 3.33 kg/s. Heating it from 20 °C to 150 °C needs 3.33 × 1.005 × 130 ≈ 435 kW.
Each kilogram of water evaporated takes roughly 2,260 kJ of latent heat, plus the heat to bring it to evaporation temperature. Removing 300 kg of water per hour:
300 kg/h ÷ 3600 × 2,260 kJ/kg ≈ 188 kW
In practice, much of the evaporation heat comes from the air in step 1 cooling as it picks up moisture. Do not simply add the two. Size from the exhaust air volume and temperature needed to carry the water away, then check the energy balance.
Add the heat to warm the product and any belt or trays (mass × specific heat × temperature rise), plus wall and opening losses. For a well-insulated dryer, 10–20% on top of the process load is a common allowance; poorly sealed older dryers can need more.
Divide the total by the system efficiency. Direct firing puts almost all of the gas energy into the air; an indirect heat exchanger loses part of it up the flue. Then add a margin for heat-up so the dryer reaches temperature in reasonable time.
Gas flow follows from the heating value. Natural gas has a lower heating value of about 36 MJ/m³ (about 10 kWh/m³); propane is about 46 MJ/kg. A 600 kW burner on natural gas therefore needs roughly 60 m³/h at full fire.